Backflow assembly test: 1998 Orchard Dr
ApprovedFiled Dec 6, 2025 by Avery Ashby, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 6, 2025
- Assembly type
- RP
- Serial number
- K586540
- Size
- 1
- Test gauge serial
- G-4456
- Gauge calibration date
- Mar 5, 2025
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ashby, current on the service date
- All required fields present
- Address matches parcel 017-40-01211
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.