Backflow assembly test: 6210 Ridgeview Rd

Approved

Filed Oct 9, 2025 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Oct 9, 2025
Assembly type
RP
Serial number
B130552
Size
1
Test gauge serial
G-1777
Gauge calibration date
Apr 5, 2025
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-50-01212
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.