Backflow assembly test: 2962 Mill Creek Way
ApprovedFiled Jul 19, 2025 by Riley Marsh, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 19, 2025
- Assembly type
- DC
- Serial number
- A481299
- Size
- 1
- Test gauge serial
- G-2377
- Gauge calibration date
- Mar 22, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Marsh, current on the service date
- All required fields present
- Address matches parcel 017-74-01030
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.