Backflow assembly test: 9007 Old Church Dr

Approved

Filed Nov 14, 2024 by Avery Wexler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 14, 2024
Assembly type
PVB
Serial number
Z627560
Size
1
Test gauge serial
G-3872
Gauge calibration date
Jul 15, 2024
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 017-57-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9007 Old Church Dr
Owner: Casey Wexler
Parcel 017-57-01327