Backflow assembly test: 1720 Sycamore Ln

Approved

Filed Mar 9, 2024 by Riley Marsh, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 9, 2024
Assembly type
DC
Serial number
A316845
Size
3/4
Test gauge serial
G-3788
Gauge calibration date
Sep 23, 2023
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Marsh, current on the service date
  • All required fields present
  • Address matches parcel 017-59-01258
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1720 Sycamore Ln
Owner: Morgan Kessler
Parcel 017-59-01258