Back to the backflow review queue

Backflow assembly test: Corner Pizza

Approved

Filed Jan 13, 2025 by Riley Marsh, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 13, 2025
Assembly type
RP
Serial number
A721845
Size
2
Test gauge serial
G-7942
Gauge calibration date
Sep 23, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Marsh, current on the service date
  • All required fields present
  • Address matches parcel 017-71-01076
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2888 Laurel Ln
Owner: Benton Holdings LLC
Parcel 017-71-01076