Backflow assembly test: Corner Pizza
ApprovedFiled Feb 17, 2026 by Parker Stroud, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Feb 17, 2026
- Assembly type
- RP
- Serial number
- A721845
- Size
- 2
- Test gauge serial
- G-9263
- Gauge calibration date
- Dec 9, 2025
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Stroud, current on the service date
- All required fields present
- Address matches parcel 017-71-01076
- Readings in range, no flags
- Result: passing. Next due date resets when approved.