Backflow assembly test: 4932 Hickory Dr
ApprovedFiled Jan 20, 2026 by Logan Fairley, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 20, 2026
- Assembly type
- DC
- Serial number
- K763354
- Size
- 1
- Test gauge serial
- G-6766
- Gauge calibration date
- Apr 24, 2025
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Fairley, current on the service date
- All required fields present
- Address matches parcel 017-91-01300
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4932 Hickory Dr
Owner: Quinn Nguyen
Parcel 017-91-01300