Back to the backflow review queue

Backflow assembly test: 6114 Pine Knoll Rd

Approved

Filed Apr 19, 2026 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 19, 2026
Assembly type
RP
Serial number
Z262485
Size
3/4
Test gauge serial
G-1690
Gauge calibration date
Aug 19, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-52-01086
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6114 Pine Knoll Rd
Owner: Cameron Wexler
Parcel 017-52-01086