Back to the backflow review queue

Backflow assembly test: 3725 Hickory Trl

Approved

Filed Apr 9, 2025 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Apr 9, 2025
Assembly type
RP
Serial number
B922193
Size
3/4
Test gauge serial
G-1942
Gauge calibration date
Jul 1, 2024
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-27-01103
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3725 Hickory Trl
Owner: Alex Ashby
Parcel 017-27-01103