Backflow assembly test: 3725 Hickory Trl
ApprovedFiled Apr 9, 2025 by Avery Ashby, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Apr 9, 2025
- Assembly type
- RP
- Serial number
- B922193
- Size
- 3/4
- Test gauge serial
- G-1942
- Gauge calibration date
- Jul 1, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ashby, current on the service date
- All required fields present
- Address matches parcel 017-27-01103
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.