Back to the backflow review queue

Backflow assembly test: 1164 Turkey Hill Ln

Approved

Filed Jul 12, 2026 by Riley Marsh, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 12, 2026
Assembly type
DC
Serial number
W192431
Size
1
Test gauge serial
G-5452
Gauge calibration date
Feb 16, 2026
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Marsh, current on the service date
  • All required fields present
  • Address matches parcel 017-87-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1164 Turkey Hill Ln
Owner: Sam Kessler
Parcel 017-87-01279