Backflow assembly test: Main Street Grill
ApprovedFiled May 9, 2026 by Parker Stroud, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- May 9, 2026
- Assembly type
- DC
- Serial number
- A983966
- Size
- 1 1/2
- Test gauge serial
- G-5289
- Gauge calibration date
- Feb 8, 2026
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Stroud, current on the service date
- All required fields present
- Address matches parcel 017-64-01047
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.