Back to the backflow review queue
Backflow assembly test: 4159 Laurel Ln
ApprovedFiled Jan 23, 2026 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 23, 2026
- Assembly type
- PVB
- Serial number
- A765429
- Size
- 1
- Test gauge serial
- G-9276
- Gauge calibration date
- Jun 20, 2025
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Ellery, current on the service date
- All required fields present
- Address matches parcel 025-30-01289
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4159 Laurel Ln
Owner: Parker Calloway
Parcel 025-30-01289