Back to the backflow review queue

Backflow assembly test: 4159 Laurel Ln

Approved

Filed Jan 23, 2026 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 23, 2026
Assembly type
PVB
Serial number
A765429
Size
1
Test gauge serial
G-9276
Gauge calibration date
Jun 20, 2025
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Ellery, current on the service date
  • All required fields present
  • Address matches parcel 025-30-01289
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4159 Laurel Ln
Owner: Parker Calloway
Parcel 025-30-01289