Backflow assembly test: 8706 Cedar Hollow Way

Approved

Filed Sep 5, 2026 by Avery Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 5, 2026
Assembly type
RP
Serial number
W582744
Size
3/4
Test gauge serial
G-2894
Gauge calibration date
May 11, 2026
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Vance, current on the service date
  • All required fields present
  • Address matches parcel 025-77-01071
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.