Back to the backflow review queue

Backflow assembly test: Maple Leaf Car Wash

Approved

Filed Jan 28, 2025 by Drew Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jan 28, 2025
Assembly type
RP
Serial number
B808370
Size
2
Test gauge serial
G-1442
Gauge calibration date
Apr 13, 2024
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 025-79-01230
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4320 Mill Creek Way
Owner: Stroud Holdings LLC
Parcel 025-79-01230