Backflow assembly test: 556 Fox Run Dr
ApprovedFiled Sep 21, 2024 by Drew Stroud, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 21, 2024
- Assembly type
- PVB
- Serial number
- B965804
- Size
- 1
- Test gauge serial
- G-6457
- Gauge calibration date
- Apr 23, 2024
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Stroud, current on the service date
- All required fields present
- Address matches parcel 025-23-01192
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.