Backflow assembly test: 556 Fox Run Dr

Approved

Filed Oct 6, 2025 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 6, 2025
Assembly type
PVB
Serial number
B965804
Size
1
Test gauge serial
G-7008
Gauge calibration date
May 14, 2025
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Ellery, current on the service date
  • All required fields present
  • Address matches parcel 025-23-01192
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.