Backflow assembly test: 8680 Hickory Way

Approved

Filed Nov 12, 2026 by Drew Stroud, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 12, 2026
Assembly type
RP
Serial number
K361885
Size
1
Test gauge serial
G-8677
Gauge calibration date
Dec 15, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.3 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 025-56-01092
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8680 Hickory Way
Owner: Cameron Calloway
Parcel 025-56-01092