Backflow assembly test: 5058 Meadow Lark Ln

Approved

Filed Jan 9, 2026 by Drew Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jan 9, 2026
Assembly type
RP
Serial number
W378063
Size
3/4
Test gauge serial
G-9364
Gauge calibration date
May 17, 2025
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 025-57-01239
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5058 Meadow Lark Ln
Owner: Hayden Harlow
Parcel 025-57-01239