ApprovedFiled Aug 22, 2026 by Avery Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 22, 2026
- Assembly type
- RP
- Serial number
- B186787
- Size
- 1
- Test gauge serial
- G-3068
- Gauge calibration date
- Mar 31, 2026
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 1.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Vance, current on the service date
- All required fields present
- Address matches parcel 025-34-01048
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.