Backflow assembly test: 3327 Sycamore Dr

Approved

Filed Sep 3, 2025 by Blake Pruitt, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Sep 3, 2025
Assembly type
DC
Serial number
Z271270
Size
1
Test gauge serial
G-2623
Gauge calibration date
Feb 13, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 025-26-01307
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.