Backflow assembly test: 8232 Mill Creek Trl

Approved

Filed Aug 30, 2025 by Parker Benton, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 30, 2025
Assembly type
RP
Serial number
W882650
Size
1
Test gauge serial
G-8386
Gauge calibration date
May 3, 2025
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Benton, current on the service date
  • All required fields present
  • Address matches parcel 025-96-01318
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8232 Mill Creek Trl
Owner: Riley Ashby
Parcel 025-96-01318