Backflow assembly test: 8831 Orchard Ct

Approved

Filed Oct 3, 2024 by Reese Fairley, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 3, 2024
Assembly type
RP
Serial number
K341065
Size
3/4
Test gauge serial
G-6617
Gauge calibration date
Apr 17, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 025-63-01170
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.