Back to the backflow review queue

Backflow assembly test: 3534 Stone Gate Way

Filed Nov 22, 2026 by Parker Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Nov 22, 2026
Assembly type
DC
Serial number
Z676876
Size
1
Test gauge serial
G-9014
Gauge calibration date
Sep 30, 2026
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Benton, current on the service date
  • All required fields present
  • Address matches parcel 025-34-01293
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

3534 Stone Gate Way
Owner: Taylor Vance
Parcel 025-34-01293