Back to the backflow review queue

Backflow assembly test: 7327 Mill Creek Ln

Approved

Filed Aug 31, 2024 by Parker Whitcomb, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Aug 31, 2024
Assembly type
PVB
Serial number
B550220
Size
1
Test gauge serial
G-2497
Gauge calibration date
Nov 20, 2023
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 037-16-01305
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7327 Mill Creek Ln
Owner: Casey Okafor
Parcel 037-16-01305