Back to the backflow review queue

Backflow assembly test: Crossroads Taqueria

Approved

Filed Jun 28, 2026 by Parker Vance, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 28, 2026
Assembly type
RP
Serial number
Z347544
Size
1 1/2
Test gauge serial
G-9259
Gauge calibration date
May 13, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-98-01323
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1491 Hickory Way
Owner: Benton Holdings LLC
Parcel 037-98-01323