Back to the backflow review queue

Backflow assembly test: 9661 Hickory Trl

Sent back

Filed Nov 20, 2026 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 20, 2026
Assembly type
DC
Serial number
Z478844
Size
1
Test gauge serial
G-6438
Gauge calibration date
May 10, 2026
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-17-01067
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Sent back Please add the test gauge calibration certificate.

Property

9661 Hickory Trl
Owner: Blake Calloway
Parcel 037-17-01067