Back to the backflow review queue

Backflow assembly test: 309 Laurel Dr

Sent back

Filed Nov 21, 2026 by Drew Kessler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 21, 2026
Assembly type
RP
Serial number
W496950
Size
3/4
Test gauge serial
G-3035
Gauge calibration date
Sep 13, 2026
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Kessler, current on the service date
  • All required fields present
  • Address matches parcel 037-25-01310
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Sent back Please add the test gauge calibration certificate.

Property

309 Laurel Dr
Owner: Quinn Ellery
Parcel 037-25-01310