Back to the backflow review queue

Backflow assembly test: 3648 Old Church Trl

Approved

Filed Aug 30, 2025 by Parker Whitcomb, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Aug 30, 2025
Assembly type
RP
Serial number
K107360
Size
3/4
Test gauge serial
G-2261
Gauge calibration date
Dec 13, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 037-60-01159
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3648 Old Church Trl
Owner: Jamie Fairley
Parcel 037-60-01159