Backflow assembly test: Hilltop Medical Offices

Approved

Filed Dec 12, 2024 by Sam Vance, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Dec 12, 2024
Assembly type
RP
Serial number
B947806
Size
4
Test gauge serial
G-2971
Gauge calibration date
Sep 13, 2024
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-13-01081
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.