Back to the backflow review queue

Backflow assembly test: Maple Leaf Bakery

Approved

Filed Dec 11, 2025 by Parker Whitcomb, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 11, 2025
Assembly type
RP
Serial number
K804861
Size
4
Test gauge serial
G-5756
Gauge calibration date
Feb 24, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 037-95-01204
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8685 Old Church Dr
Owner: Danner Holdings LLC
Parcel 037-95-01204