Backflow assembly test: 8502 Fox Run Way

Approved

Filed Oct 6, 2025 by Parker Whitcomb, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 6, 2025
Assembly type
PVB
Serial number
B227444
Size
3/4
Test gauge serial
G-5457
Gauge calibration date
Aug 8, 2025
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 037-32-01357
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.