Backflow assembly test: Maple Leaf Market
Needs reviewFiled Nov 21, 2026 by Hayden Pruitt, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 21, 2026
- Assembly type
- RP
- Serial number
- W764151
- Size
- 4
- Test gauge serial
- G-3340
- Gauge calibration date
- Apr 3, 2026
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Pruitt, current on the service date
- All required fields present
- Address matches parcel 037-60-01330
- Readings in range, no flags
- Result: passing. Next due date resets when approved.