Backflow assembly test: 438 Hickory Way

Approved

Filed Dec 8, 2024 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 8, 2024
Assembly type
RP
Serial number
Z411685
Size
3/4
Test gauge serial
G-6838
Gauge calibration date
Sep 13, 2024
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-74-01053
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

438 Hickory Way
Owner: Logan Benton
Parcel 037-74-01053