Back to the backflow review queue

Backflow assembly test: 2592 Pine Knoll Trl

Approved

Filed Apr 21, 2026 by Parker Vance, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 21, 2026
Assembly type
RP
Serial number
A624684
Size
3/4
Test gauge serial
G-4266
Gauge calibration date
Jun 29, 2025
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-68-01176
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2592 Pine Knoll Trl
Owner: Jordan Ramirez
Parcel 037-68-01176