Backflow assembly test: Two Rivers Elementary School

Approved

Filed Jan 23, 2026 by Casey Fairley, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 23, 2026
Assembly type
RP
Serial number
A575327
Size
2
Test gauge serial
G-6540
Gauge calibration date
Aug 11, 2025
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-81-01233
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6145 Fox Run Dr
Owner: Brandt Holdings LLC
Parcel 041-81-01233