Backflow assembly test: Golden Elementary School

Approved

Filed Jun 1, 2026 by Casey Fairley, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 1, 2026
Assembly type
RP
Serial number
A382945
Size
4
Test gauge serial
G-4946
Gauge calibration date
Oct 20, 2025
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-56-01110
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9507 Laurel Rd
Owner: Stroud Holdings LLC
Parcel 041-56-01110