Backflow assembly test: 9864 Sycamore Trl

Approved

Filed Mar 21, 2025 by Quinn Nguyen, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Mar 21, 2025
Assembly type
RP
Serial number
W636252
Size
3/4
Test gauge serial
G-7443
Gauge calibration date
Nov 25, 2024
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 041-22-01336
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.