Backflow assembly test: 2866 Orchard Dr

Approved

Filed May 15, 2024 by Casey Fairley, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 15, 2024
Assembly type
RP
Serial number
Z875001
Size
1
Test gauge serial
G-9144
Gauge calibration date
Sep 10, 2023
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-71-01036
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2866 Orchard Dr
Owner: Blake Danner
Parcel 041-71-01036