Backflow assembly test: 1960 Meadow Lark Trl
ApprovedFiled Oct 26, 2025 by Parker Ashby, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 26, 2025
- Assembly type
- RP
- Serial number
- A646434
- Size
- 1
- Test gauge serial
- G-9000
- Gauge calibration date
- Jul 21, 2025
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 041-34-01046
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1960 Meadow Lark Trl
Owner: Jamie Lindqvist
Parcel 041-34-01046