Back to the backflow review queue

Backflow assembly test: 1061 Meadow Lark Trl

Approved

Filed Jun 25, 2026 by Quinn Nguyen, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Jun 25, 2026
Assembly type
DC
Serial number
Z260241
Size
3/4
Test gauge serial
G-9596
Gauge calibration date
Feb 17, 2026
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 041-46-01151
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1061 Meadow Lark Trl
Owner: Sam Ramirez
Parcel 041-46-01151