Back to the backflow review queue

Backflow assembly test: 8006 Mill Creek Dr

Approved

Filed Aug 8, 2025 by Quinn Nguyen, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Aug 8, 2025
Assembly type
RP
Serial number
B390155
Size
3/4
Test gauge serial
G-7723
Gauge calibration date
Apr 17, 2025
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
1.5 psid
Relief valve opened at
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 041-62-01140
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8006 Mill Creek Dr
Owner: Casey Brandt
Parcel 041-62-01140