Backflow assembly test: 9260 Mill Creek Way

Approved

Filed Dec 5, 2024 by Avery Wexler, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Dec 5, 2024
Assembly type
RP
Serial number
A954446
Size
1
Test gauge serial
G-3350
Gauge calibration date
Feb 5, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 041-39-01187
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9260 Mill Creek Way
Owner: Blake Benton
Parcel 041-39-01187