Backflow assembly test: 9260 Mill Creek Way
ApprovedFiled Dec 28, 2025 by Morgan Pruitt, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 28, 2025
- Assembly type
- RP
- Serial number
- A954446
- Size
- 1
- Test gauge serial
- G-9896
- Gauge calibration date
- Jun 15, 2025
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Pruitt, current on the service date
- All required fields present
- Address matches parcel 041-39-01187
- Readings in range, no flags
- Result: passing. Next due date resets when approved.