Backflow assembly test: 1105 Turkey Hill Ln

Approved

Filed Jul 11, 2025 by Parker Ashby, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 11, 2025
Assembly type
RP
Serial number
W404280
Size
3/4
Test gauge serial
G-6137
Gauge calibration date
Nov 27, 2024
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 041-40-01256
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1105 Turkey Hill Ln
Owner: Parker Kessler
Parcel 041-40-01256