Back to the backflow review queue

Backflow assembly test: 1105 Turkey Hill Ln

Approved

Filed Jul 27, 2026 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jul 27, 2026
Assembly type
RP
Serial number
W404280
Size
3/4
Test gauge serial
G-2888
Gauge calibration date
Mar 22, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-40-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1105 Turkey Hill Ln
Owner: Parker Kessler
Parcel 041-40-01256