Backflow assembly test: 9667 Cedar Hollow Ln

Approved

Filed Dec 19, 2023 by Morgan Pruitt, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 19, 2023
Assembly type
RP
Serial number
W100853
Size
3/4
Test gauge serial
G-8801
Gauge calibration date
Sep 5, 2022
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Relief valve opened at
3.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 041-35-01258
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9667 Cedar Hollow Ln
Owner: Quinn Wexler
Parcel 041-35-01258