Backflow assembly test: 9718 Old Church Ct
ApprovedFiled Jan 4, 2024 by Parker Harlow, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Jan 4, 2024
- Assembly type
- RP
- Serial number
- W348836
- Size
- 1
- Test gauge serial
- G-6016
- Gauge calibration date
- Oct 7, 2023
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Harlow, current on the service date
- All required fields present
- Address matches parcel 041-59-01206
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.