Backflow assembly test: 3057 Quarry Rd

Approved

Filed Sep 21, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 21, 2025
Assembly type
DC
Serial number
B443082
Size
3/4
Test gauge serial
G-1300
Gauge calibration date
Nov 28, 2024
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-11-01155
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3057 Quarry Rd
Owner: Emerson Calloway
Parcel 051-11-01155