Backflow assembly test: 6070 Orchard Rd
ApprovedFiled Jun 3, 2024 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 3, 2024
- Assembly type
- PVB
- Serial number
- K965461
- Size
- 1
- Test gauge serial
- G-7462
- Gauge calibration date
- Mar 28, 2023
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-25-01017
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.